- 156: Adams, Site tower, Fri 21-Feb-2003 14:04:08 MST, Cosmos ADAM fan replaced
At 13:45 the old Cosmos ADAM fan was definately not operating. It could be
started by poking it with a screwdriver but would soon stop.
The spare fan was employed as a replacement.
- 148: Adams, Site tower, Wed 19-Feb-2003 12:26:10 MST, COSMOS rebooted
COSMOS was rebooted to download the new channel config defining
channel 211. This took place around 11:10 am local.
- 143: Adams, Site tower, Tue 18-Feb-2003 17:55:50 MST, cosmos down at 1:30 pm local
Cosmos was powered down at about 1:30 pm local to add
analog boards. It was back up around 1:45 pm local.
- 126: Adams, Site tower, Tue 28-Jan-2003 15:00:59 MST, Cosmos Cooler / overheating fixed
1/28/03 The outboard fan on the TECA coolers was bad
and was replaced. This hopefully should fix the problem
so we won't get anymore lockups.
SteveS thinks that the cooler was working ok otherwise
based on the data.
NOTE: several adam power cycles this morning because of this
work. Blew breaker trying to heat test the thermostat. then
a few other cycles while playing around and swapping the fan.
- 57: Adams, Site tower, Mon 16-Dec-2002 12:18:20 MST, Power glitch caused adam crash
Daisy and cosmos crashed last night due to a power glich. Here's
what the UPS reported in the system log. These times are MST:
Dec 16 00:59:37 aster upsd[1546]: UPS on battery
Dec 16 00:59:37 aster upsd[1546]: Normal power restored: UPS on line
Dec 16 00:59:40 aster upsd[1546]: UPS on battery: Deep momentary sag 108.5 V
Dec 16 00:59:40 aster upsd[1546]: Normal power restored: UPS on line
- 10: Adams, Site tower, Fri 08-Nov-2002 21:22:39 MST, Cosmos
Cosmos
VME backplane #3
Matrix 9013
Ironics 422016
Datel 320689
Peltier cooler #2
VME Power supply: Tracer 298
Breezecom C
Boots ok, looks good
- 9: Adams, Site tower, Fri 08-Nov-2002 20:42:17 MST, Daisy
Daisy
VME chassis #2
Matrix 9006
Ironics 821003
Datel 320589
Power supply questionable (rocker switch feels weird): Tracer 238
Teca: new 0033316
Breezecom B
Netgear ethernet hub getting power from backplane
Booted ok, but after about an hour, started getting errors:
interrupt: med0: receive buffer overflow, all buffers cleared.
Errors happened at bootup, before VxWorks logo is displayed, and
afterwards. pings were erratic.
Network was through breezecom, on separate 192.168.10 subnet
DS11 statistics looked good. Did not help to bypass breezecom
and go straight into hub.
Swapped in Matrix 9009. No errors, looking good.
ingest_control -i daisy shows 310 samples/sec
Data_stats look good: 4 sonics @ 60hz, 5 TRHs, one CR10:
data_stats < dai021109.035234
Opened:
chan #points start time end time delta time freq
0 23 03:52:34.470 03:56:15.030 220.560 0.100
100 4406 03:52:35.480 03:56:15.720 220.240 20.001
101 4406 03:52:35.480 03:56:15.720 220.240 20.001
102 4406 03:52:35.480 03:56:15.720 220.240 20.001
107 221 03:52:35.480 03:56:15.470 219.990 1.000
200 11327 03:53:06.970 03:56:15.740 188.770 59.999
201 11328 03:53:06.960 03:56:15.760 188.800 59.995
202 11329 03:53:06.940 03:56:15.750 188.810 59.997
203 11303 03:53:07.350 03:56:15.750 188.400 59.989
204 209 03:52:47.130 03:56:15.020 207.890 1.001
205 209 03:52:47.090 03:56:15.050 207.960 1.000
206 210 03:52:46.230 03:56:15.190 208.960 1.000
207 210 03:52:46.240 03:56:15.210 208.970 1.000
208 210 03:52:46.240 03:56:15.210 208.970 1.000
209 42 03:52:47.680 03:56:12.680 205.000 0.200